|
|
|
|
Electrical utility engineers and project
managers that require a cost effective serial-to-Ethernet solution to
help meet NERC-CIP compliance for the protection of critical cyberassets
in substations must consider the IOLAN SDS HV/LDC Terminal Server.
In addition to the most extensive security features available, these
IOLANs are designed to meet harsh environments associated with Power
Substations with attributes such as support for substation AC and DC
voltage ranges, extended operating temperatures and meeting emission,
immunity and safety approvals associated with substation IT equipment.
Ideal for
- Electrical utility engineers and
Project Managers requiring a high performance serial to Ethernet
interface for serial RS232 or RS485 based devices such as SCADA based
RTUs and protection relays.
- Environments that require a serial terminal server with unique environmental, form factor, or power inputs in harsh environments
- Substation Automation projects where using secured communications in remote connections is required.
Why IOLAN SDS HV/LDC Terminal Servers are the preferred choice:
- NERC CIP compliance features (EPCIP EU COM(2006)786);
- TACACS+, RADIUS for centralized authentication, authorization and accounting
- Support for alternate TACACS+ and RADIUS hosts
- Two factor strong authentication such as RSAs SecureID
- HTTPS, SSL/TLS, SSH ( AES, 3DES ) session encryption
- Keystroke and data logging
- Provides the ability to display a customizable Appropriate Use login banner upon user access
- Secure dial-up
- Enable only the serial ports you need
- Meets IEC 61850-3 and IEEE 1613 ( IEEE C37 90 ) electrical substation EMI standards
- FIPS 140-2 Cryptographic modules meet US Government NIST compliancy
- Universal High voltage: 88-300v DC or 85-265v AC dual power models
- Dual Feed low voltage: 18 - 72v DC models
- Cisco RJ45 serial port pinout design enables connection to Cisco/Sun console ports using common serial rolled CAT5 cabling
- Encapsulate ModBus and DNP protocols over IP
- Modbus TCP to Modbus RTU/ASCII gateway
- High performance 400 Mhz, 750 MIPS, 32
bit processor with integrated hardware encryption processor for the
best throughput on the market
- Next Generation IP support (IPv6 ) for investment protection and network compatibility
- TrueSerial packet technology the most authentic serial connections across Ethernet ensures serial protocol integrity
- Primary/Backup host functionality enables automatic connections to alternate hosts should the primary TCP connection go down
- EasyPort Web Access equipment serial console ports by using
your java-enabled Internet browser
- TruePort Perles com/tty redirector for serial based applications
operates on Windows, Vista, Linux, Solaris, SCO and Unix
- Java-free browser access to remote serial console ports via Telnet and SSH
- Lifetime warranty best investment protection available
Hardware Specifications - IOLAN SDSC Electric Utility Terminal Servers
|
SDS8C
HV |
SDS8C
DHV |
SDS16C
HV |
SDS16C
DHV |
SDS32C
HV |
SDS32C
DHV |
SDS8C
LDC |
SDS16C
LDC |
SDS32C
LDC |
Processor |
MPC8349E, 400 Mhz, 750 MIPS |
Memory |
RAM MB |
64 |
64 |
64 |
64 |
128 |
128 |
64 |
64 |
64 |
Flash MB |
|
|
|
|
|
|
|
16 |
|
Interface Ports |
Number of Serial Ports |
8 |
8 |
16 |
16 |
32 |
32 |
8 |
16 |
32 |
Serial Port Interface |
Software selectable RS232 / RS485 / RS422 DTE on RJ45 - RS485: full and half duplex |
Sun / Solaris |
Sun break safe |
Serial Port Speeds |
50bps to 230Kbps with customizable
baud rate support |
Data Bits |
5,6,7,8, 9-bit protocol support |
Parity |
Odd, Even, Mark, Space, None |
Flow Control |
Hardware, Software, Both, None |
Local Console Port |
RS232 on RJ45 with DB9 adapter ( provided
) |
Network |
Dual 10/100/1000-base TX Ethernet RJ45 |
Software selectable Ethernet speed
10/100/1000, Auto |
Software selectable Half/Full/Auto
duplex |
Failsafe Alarm Relay |
3A@24v DC. Normally open contacts closed by IOLAN when active and opened upon alarm condition or power failure |
Power |
Power Supply |
Terminal Block with screw terminals accommodating a #6 ring terminal for each power source. Protective cover provided |
Plugable Terminal Blocks with screw terminals accommodating 28 - 12 AWG wire sizes |
Nominal Input Voltage |
125V DC / 250V DC or 100V AC / 240V AC |
24v DC / 48v DC |
Input Voltage Range |
88-300V DC or 85-265V AC |
18 - 72v DC |
AC Input Frequency |
47-63Hz |
Current Consumption @ 125v DC (Amps) |
0.06 |
0.07 |
0.08 |
0.08 |
0.13 |
0.13 |
N/A |
N/A |
N/A |
Current Consumption @ 250v DC (Amps) |
0.04 |
0.04 |
0.05 |
0.05 |
0.07 |
0.07 |
N/A |
N/A |
N/A |
Current Consumption @ 115v AC (Amps) |
0.13 |
0.15 |
0.07 |
0.2 |
0.26 |
0.28 |
N/A |
N/A |
N/A |
Current Consumption @ 230v AC (Amps) |
0.09 |
0.11 |
0.12 |
0.14 |
0.16 |
0.19 |
N/A |
N/A |
N/A |
Current Consumption @ 18v DC (Amps) |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
0.4 |
0.55 |
0.85 |
Current Consumption @ 24v DC (Amps) |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
0.3 |
0.4 |
0.65 |
Current Consumption @ 48v DC (Amps) |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
0.2 |
0.25 |
0.35 |
Current Consumption @ 72v DC (Amps) |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
0.15 |
0.18 |
0.25 |
Typical Power Consumption (Watts) |
9 |
10 |
12 |
12.5 |
17 |
17.5 |
11 |
13 |
18 |
Chassis Ground |
Grounding screw for a #10 ring terminal |
Indicators |
LEDs |
Power |
System Ready |
Network Link activity |
Serial: Transmit and Receive data per
port |
Environmental Specifications |
Heat Output ( BTU/HR ) |
30.7 |
34.12 |
40.9 |
42.7 |
58 |
59.7 |
37.6 |
44.4 |
61.5 |
MTBF ( Hours ) |
144,323 |
126,121 |
117,779 |
105,368 |
89,711 |
82,325 |
126,302 |
105,495 |
82,402 |
Operating Temperature |
-40C ambient for 16 hours and +70C ambient for 16 hours without use of fans |
Storage Temperature |
-40C to 85C, -40F to 185F |
Humidity |
5 to 95% (non condensing) for both storage and operation. |
Case |
SECC Zinc plated sheet metal (1 mm) |
Ingress Protection Rating |
IP30 |
Mounting |
1U - 19" rack, front and rear mounting hardware included.
DIN Rail mounting kit optional |
Product Weight and Dimensions |
Weight |
3.20 kg |
3.38 kg |
3.22 kg |
3.40 kg |
3.40 kg |
3.58 kg |
3.16 kg |
3.18 kg |
3.36 kg |
Dimensions |
1U Rack form factor - 26.4 x 43.4 x
4.4 (cm), 10.38 x 17.1 x 1.75 (in) |
Packaging |
Shipping Dimensions |
59 x 36 x 9 (cm), 23 x 14 x 3.5 (in) |
Shipping Weight |
4.00 kg |
4.18 kg |
4.20 kg |
4.20 kg |
4.20 kg |
4.38 kg |
3.96 kg |
3.98 kg |
4.16 kg |
Regulatory Approvals |
Emissions |
Power Line conducted: IEC 61850-3 Sec 5.8, IEC 61000-6-4,
CISPR 16-2-3, CISPR 22, FCC Part 15,
Subpart B, Class B |
Telecom Line conducted: IEC 61000-6-4, CISPR 22 |
Radiated: IEC 61850-3 Sec 5.8, IEC 61000-6-4,
CISPR 16-2-3, CISPR 22, FCC Part 15, Subpart B, Class B |
IEC61000-3-2 Harmonic Current Emissions |
IEC61000-3-3 Flicker emissions |
EMC Interface Immunity
- IEC 61850-3
( substations )
- IEEE 1613 ( substations ) (C37.90.x )
Applies to
all ports, signal and power connections |
ESD: IEC61000-4-2, 8Kv Contact / 15Kv Air |
Radiated RFI: IEC61000-4-3, 20 V/m ( 80M-1G ) |
Fast Transients / Burst: IEC61000-4-4, 4Kv Mains , I/O |
Surge : IEC61000-4-5
4Kv AC line to Gnd, 2Kv AC Line to Line,
2Kv DC line to Gnd, 1 Kv DC Line to Line,
RS232 = balanced, ethernet = unbalanced |
Conducted RF: IEC61000-4-6, 10 Vrms |
Magnetic Field: IEC61000-4-8, 100 A/m, 1000 A/m (1 sec) |
Dips and Interrupts: IEC61000-4-11, Criteria A/B/C |
Oscillatory: EN61000-4-12, 2.5Kv common and differential mode |
Low Frequency conducted: EN61000-4-16, 30V 60s, 300V 1s,15Hz-150KHz @ level 3 |
Standard Safety Certifications |
IEC 60950-1, First Edition (2001-10)
and EN60950-1:2001, CB scheme. |
CAN/CSA-C22.2 No. 60950-1-03 and ANSI/UL
60950-1,
First Edition April 1st 2003 (Recognized Component) |
Other |
RoHS - 2002/95/EC Directive |
WEEE - 2002/96/EC Directive |
CCATS - G052929 |
ECCN - 5A992A |
HTSUS Number: 8471.80.1000 |
Perle Lifetime Warranty |
Serial Connector Pinout |
IOLAN DTE
RJ45 Socket |
IOLAN
RJ45 Socket |
Direction |
RS232 |
RS422 |
RS485
Full Duplex |
RS485
Half Duplex |
1 |
|
RTS |
TXD+ |
TXD+ |
Data+ |
2 |
|
DTR |
|
|
|
3 |
|
TXD |
TXD- |
TXD- |
Data- |
4 |
--- |
GND |
GND |
GND |
GND |
5 |
--- |
GND |
GND |
GND |
GND |
6 |
|
RXD |
RXD+ |
RXD+ |
|
7 |
|
DSR |
|
|
|
8 |
|
CTS |
RXD- |
RXD- |
|
A "rolled" CAT5 cable will automatically perform DTE to DCE crossover
Optional
Perle adapters for use with straight thru CAT5 cabling |
|
|
|
|
|
|
|
|
|
|
|
|
|
Features
Serial Port Access |
|
Connect directly using Telnet / SSH by port and IP address |
Connect with EasyPort menu by Telnet / SSH |
Use an internet browser to access with HTTP or secure HTTPS via EasyPort Web menu |
Java-free browser access to remote serial console ports via Telnet and SSH |
Ports can be assigned a specific IP address ( aliasing ) |
Multisession capability enables multiple users to access ports simultaneously |
Multihost access enables multiple hosts/servers to share serial ports |
Accessibility |
|
In-band ( Ethernet ) and out-of-band ( dial-up modem ) support |
Dynamic DNS enables users to find a console server from anywhere on the Internet |
Domain name control through DHCP option 81 |
IPV6 and IPV4 addressing support |
Availability |
|
Primary/Backup host functionality enables automatic connections to alternate host(s) |
Security |
|
SSH v1 and v2 |
SSL V3.0/TLS V1.0, SSL V2.0 |
SSL Server and SSL client mode capability |
SSL Peer authentication |
IPSec VPN : NAT Traversal, ESP authentication protocol |
Encryption: AES (256/192/128), 3DES, DES, Blowfish, CAST128, ARCFOUR(RC4), ARCTWO(RC2) |
Hashing Algorithms: MD5, SHA-1, RIPEMD160, SHA1-96, and MD5-96 |
Key exchange: RSA, EDH-RSA, EDH-DSS, ADH |
X.509 Certificate verification: RSA, DSA |
Certificate authority (CA) list |
Local database |
RADIUS Authentication, Authorization and Accounting |
TACACS+ Authentication, Authorization and Accounting |
LDAP, NIS, Kerberos Authentication |
RSA SecureID-agent or via RADIUS Authentication |
SNMP v3 Authentication and Encryption support |
IP Address filtering |
Disable unused daemons |
Active Directory via LDAP |
Terminal Server |
|
Telnet |
SSH v1 and v2 |
Rlogin |
Auto session login |
LPD, RCP printer |
MOTD - Message of the day |
Serial machine to Ethernet |
|
Tunnel raw serial data across Ethernet - clear or encrypted |
Raw serial data over TCP/IP |
Raw serial data over UDP |
Serial data control of packetized data |
Share
serial ports with multiple hosts/servers |
Virtual modem simulates a modem connection - assign IP address by AT
phone number |
Virtual modem data can be sent over the Ethernet link with or without
SSL encryption |
TruePort com/tty redirector for serial based applications on Windows,
Vista, Linux, Solaris, SCO and HP UX. For latest drivers click here
|
"TrueSerial packet technology
provides the most authentic serial connections across Ethernet ensuring
serial protocol integrity" |
RFC 2217 standard for transport of serial data and RS232 control signals |
Customizable or fixed serial baud rates |
Plug-ins allow customer or Perle provided plug-ins for special applications |
Software Development Kit
( SDK ) available |
Serial encapsulation of industrial protocols such as ModBus, DNP3 and IEC-870-5-101 |
ModBus
TCP gateway enables serial Modbus ASCII/RTU device connection to ModBus
TCP |
Data logging will store serial
data received when no active TCP session and forward to network peer
once session re-established - 32K bytes circular per port |
Console Management |
|
Sun Break Safe |
Local port buffer viewing - 256K bytes per port |
External port buffering via NFS, encrypted NFS and Syslog |
Event notification |
Manage
AC power of external equipment using Perle RPS power management products |
Clustering
- central console server enables access ports across multiple console
servers |
Windows Server 2003/2008
EMS - SAC support GUI access to text-based Special Administrative Console |
Ping watchdog probes
enable customers to power cycle equipment with attached Perle RPS power
switches in the event of an unresponsive networking gear |
Remote Access |
Dial, direct serial |
PPP, PAP/CHAP, SLIP |
|
HTTP tunneling enables firewall-safe access to remote serial devices across the internet |
Automatic DNS Update |
Utilize DHCP Opt 81 to set IOLAN domain name for easy name management
and with Dynamic DNS support , users on the Internet can access the device
server by name without having to know its IP address. See Automatic
DNS update support for details |
IPSEC VPN client/servers |
Microsoft L2TP/IPSEC VPN client ( native to Windows XP) |
Microsoft IPSEC VPN Client ( native to Windows Vista ) |
Cisco routers with IPSEC VPN feature set |
Perle IOLAN SDS/STS and SCS models |
OA&M ( Operations, Administration and Management ) |
|
SNMP V3 - read and write, Perle MIB |
Syslog |
Perle Device Manager - Windows based utility for large scale deployments |
Configurable default configuration |
Installation Wizard |
Set a Personalized Factory Default for your IOLANs |
Protocols |
|
IPv6, IPv4, TCP/IP, Reverse SSH, SSH, SSL, IPSec/IPv4,
IPSec/IPv6, L2TP/IPSec, CIDR, RIPV2/MD5, ARP, RARP, UDP, UDP Multicast,
ICMP, BOOTP, DHCP, TFTP, SFTP, SNTP, Telnet, raw, reverse Telnet, LPD,
RCP, DNS, Dynamic DNS, WINS, HTTP, HTTPS, SMTP, SNMPV3, PPP, PAP/CHAP,
SLIP, CSLIP, RFC2217, MSCHAP |
|
|
|
|
|
|
|