Environmental Product Compliance
|
REACH SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
General
|
Net weight
|
0.7 kg
|
Efficiency
|
> 92 %
|
Insulation voltage input/output
|
1.5 kV (type test)
|
|
1 kV (routine test)
|
Protection class
|
III
|
Degree of protection
|
IP20
|
MTBF (IEC 61709, SN 29500)
|
|
|
890471,95 h (40 °C)
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: P
N ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: P
N <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
|
Standards and Regulations
|
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Noise immunity
|
EN 61000-6-2:2005
|
Connection in acc. with standard
|
CUL
|
Standards/regulations
|
EN 61000-4-2
|
Contact discharge
|
4 kV (Test Level 2)
|
Standards/regulations
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
10 V/m
|
Frequency range
|
1.4 GHz ... 2 GHz
|
Test field strength
|
3 V/m
|
Standards/regulations
|
EN 61000-4-4
|
Comments
|
Criterion B
|
Standards/regulations
|
EN 61000-6-3
|
|
EN 61000-4-6
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Standard - Electrical safety
|
EN 60950-1/VDE 0805 (SELV)
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
|
EN 50178/VDE 0160 (PELV)
|
Standard – Safety extra-low voltage
|
EN 60950-1 (SELV)
|
|
EN 60204-1 (PELV)
|
Standard - Safe isolation
|
DIN VDE 0100-410
|
Shipbuilding approval
|
DNV GL (EMC B)
|
UL approvals
|
UL/C-UL listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
Shock
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
Vibration (operation)
|
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
|
|
15 Hz ... 150 Hz, 2.3g, 90 min.
|
Rail applications
|
EN 50121-4
|
ATEX
|
II 3 G Ex ec IIC T4 Gc
|
|
TÜV 13 ATEX 114239X
|
IECEx
|
Ex ec IIC T4 Gc
|
|
IECEx TUN 13.0025X
|
Connection data, input
|
Connection method
|
Pluggable screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
12
|
Stripping length
|
8 mm
|
Screw thread
|
M3
|
Output data
|
Nominal output voltage
|
24 V DC ±1 %
|
Setting range of the output voltage (U
Set)
|
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
|
Nominal output current (I
N)
|
5 A (-25 °C ... 60 °C)
|
POWER BOOST (I
Boost)
|
6.25 A (-25°C ... 40°C permanent, U
OUT = 24 V DC )
|
Selective Fuse Breaking (I
SFB)
|
30 A (12 ms)
|
Derating
|
60 °C ... 70 °C (2.5%/K)
|
Connection in parallel
|
Yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback resistance
|
35 V DC
|
Protection against surge voltage on the output
|
< 35 V DC
|
Max. capacitive load
|
Unlimited
|
Active current limitation
|
Approximately 7.2 A
|
Control deviation
|
< 1 % (change in load, static 10 % ... 90 %)
|
|
< 2 % (change in load, dynamic 10 % ... 90 %)
|
|
< 0.1 % (change in input voltage ±10 %)
|
Residual ripple
|
< 20 mV
PP
|
Peak switching voltages nominal load
|
< 10 mV
PP (20 MHz)
|
Maximum power dissipation in no-load condition
|
2.4 W
|
Power loss nominal load max.
|
11.4 W
|
Connection data for signaling
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
12
|
Screw thread
|
M3
|
Dimensions
|
Width
|
32 mm
|
Height
|
130 mm
|
Depth
|
125 mm
|
Width with alternative assembly
|
122 mm
|
Height with alternative assembly
|
130 mm
|
Depth with alternative assembly
|
35 mm
|
Weight per piece
|
865.0 GRM
|
Input data
|
Nominal input voltage range
|
24 V DC
|
Input voltage range
|
18 V DC ... 32 V DC
|
Current consumption
|
7 A (24 V, I
BOOST)
|
Inrush surge current
|
typ. 15 A
|
Mains buffering
|
typ. 10 ms (24 V DC)
|
Input fuse
|
15 A (device protection)
|
Choice of suitable circuit breakers
|
10 A ... 16 A (Characteristics B, C, D, K)
|
Type of protection
|
Transient surge protection
|
Protective circuit/component
|
Varistor
|
Connection data, onput
|
Connection method
|
Pluggable screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
12
|
Stripping length
|
7 mm
|
Screw thread
|
M3
|
Ambient conditions
|
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
100 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Approvals
|
|
- ABS
- BV
- RINA
- cUL Recognized
- cUL Listed
- LR
- UL Listed
- cULus Listed
- UL Recognized
- EAC
- cULus Recognized
- NK
- DNV
Nominal voltage U
N
|
750 V
|
|
|
|
|
Nominal current I
N
|
15 A
|
|
|
|
|
mm²/AWG/kcmil
|
4
|
|
|
|
|
|