Ambient conditions
|
Ambient temperature (operation)
|
-20 °C ... 60 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Permissible humidity (operation)
|
30 % ... 95 % (non-condensing)
|
Altitude
|
5000 m (For restrictions see manufacturer's declaration)
|
Degree of protection
|
IP20
|
Noise immunity
|
EN 61000-6-2:2005
|
Standards and Regulations
|
Electromagnetic compatibility
|
Conformance with EMC directive 89/336/EC
|
Type of test
|
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6
|
Test result
|
5g, 10-150 Hz, 2.5 h, in XYZ direction
|
Type of test
|
Shock in acc. with EN 60068-2-27/IEC 60068-2-27
|
Test result
|
15g, 11 ms period, half-sine shock pulse
|
Shock
|
15g in all directions in acc. with IEC 60068-2-27
|
Noise emission
|
EN 55011
|
Noise immunity
|
EN 61000-6-2:2005
|
Connection in acc. with standard
|
CUL
|
Standards/regulations
|
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
|
Vibration (operation)
|
In acc. with IEC 60068-2-6: 5g, 150 Hz
|
Conformance
|
CE-compliant
|
ATEX
|
II 3 G Ex nA nC IIC T4 Gc X
|
UL, USA/Canada
|
508 listed
508 recognized
|
Free from substances that could impair the application of coating
|
according to P-VW 3.10.7 57 65 0 VW-AUDI-Seat central standard
|
Optical interface FO
|
Number of FO ports
|
1
|
Wavelength
|
1300 nm
|
Transmission length incl. 3 dB system reserve
|
27 km (With F-G 50/125 0.7 dB/km at 1300 nm)
22 km (with F-G 62.5/125 0.8 dB/km at 1300 nm)
45 km (With F-E 9/125 0,4 dB/km at 1300 nm)
|
Transmission medium
|
Multi-mode fiberglass
Single-mode fiberglass
|
Transmission protocol
|
Transparent to protocol for RS-422 interface
|
Connection method
|
SC duplex
|
General
|
Transmission channels
|
2 (1/1) RD, TD, full duplex
|
Bit distortion, input
|
± 35 % (permitted)
|
Bit distortion, output
|
< 6.25 %
|
Electrical isolation
|
VCC // RS-422
|
Test voltage data interface/power supply
|
1.5 kVrms (50 Hz, 1 min.)
|
Electromagnetic compatibility
|
Conformance with EMC directive 89/336/EC
|
Noise emission
|
EN 55011
|
Net weight
|
190.68 g
|
Housing material
|
PA 6.6-FR
|
Color
|
green
|
MTBF
|
544 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
113 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
|
Conformance
|
CE-compliant
|
ATEX
|
II 3 G Ex nA nC IIC T4 Gc X (Please follow the special installation instructions in the documentation!)
|
UL, USA/Canada
|
508 listed
508 recognized
|
Digital outputs
|
Output name
|
Relay output
|
Output description
|
Alarm output
|
Number of outputs
|
1
|
Maximum switching voltage
|
60 V DC
42 V AC
|
Limiting continuous current
|
1:00 AM
|
Power supply
|
Nominal supply voltage
|
24 V DC (With UL approval)
|
Supply voltage range
|
18 V DC ... 32 V DC
|
Typical current consumption
|
110 mA (24 V DC)
|
Connection method
|
COMBICON plug-in screw terminal block
|
Serial interface
|
Interface 1
|
RS-422 interface in acc. with ITU-T V.11, EIA/TIA-422, DIN 66348-1
|
Operating mode
|
Full duplex
|
Connection method
|
Pluggable screw connection
|
Transmission medium
|
Copper
|
Transmission length
|
≤ 1000 m (depending on the data rate, with shielded, twisted data cable)
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
14
|
Serial transmission speed
|
≤ 2 Mbps
|
Dimensions
|
Width
|
35 mm
|
Height
|
105 mm
|
Depth
|
103 mm
|
|
|
Environmental Product Compliance
|
China RoHS
|
Environmentally Friendly Use Period = 50
|
Reach and RoHS Compliant
|
Reach and RoHS Compliant
|
Approvals
|
|
cUL Listed
cULus Listed
UL Listed
ATEX
EAC
DNV
cUL Recognized
cULus Recognized
UL Recognized
|
Commercial data
|
Packing unit
|
1
|
Weight per piece
|
229.6 g
|
Country of origin
|
Germany
|
Warranty
|
1 Year
|