Environmental Product Compliance
|
REACH SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
General
|
Net weight
|
3.3 kg
|
Efficiency
|
> 93 % (for 230 V AC and nominal values)
|
Insulation voltage input/output
|
4 kV AC (type test)
|
|
2 kV AC (routine test)
|
Insulation voltage input / PE
|
3.5 kV AC (type test)
|
|
2 kV AC (routine test)
|
Insulation voltage output / PE
|
500 V DC (routine test)
|
Protection class
|
I
|
Degree of protection
|
IP20
|
MTBF (IEC 61709, SN 29500)
|
> 880000 h (25 °C)
|
|
> 523000 h (40 °C)
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: P
N ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: P
N <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
|
Standards and Regulations
|
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Noise emission
|
EN 55011 (EN 55022)
|
Noise immunity
|
EN 61000-6-2:2005
|
Connection in acc. with standard
|
CSA
|
Standards/regulations
|
EN 61000-4-2
|
Contact discharge
|
4 kV (Test Level 2)
|
Standards/regulations
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
1.4 GHz ... 2 GHz
|
Test field strength
|
3 V/m (Test Level 2)
|
Standards/regulations
|
EN 61000-4-4
|
Comments
|
Criterion B
|
Standards/regulations
|
EN 61000-6-3
|
|
EN 61000-4-6
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Low Voltage Directive
|
Conformance with LV directive 2006/95/EC
|
Standard - Electrical safety
|
IEC 60950-1/VDE 0805 (SELV)
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
|
EN 50178/VDE 0160 (PELV)
|
Standard – Safety extra-low voltage
|
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
|
Standard - Safe isolation
|
DIN VDE 0100-410
|
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
|
EN 50178
|
Standard – Limitation of mains harmonic currents
|
EN 61000-3-2
|
Standard - Equipment safety
|
BG (design tested)
|
Shipbuilding approval
|
DNV GL (EMC A)
|
UL approvals
|
UL Listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
Shock
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
Vibration (operation)
|
< 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
|
|
15 Hz ... 150 Hz, 2.3g, 90 min.
|
Information technology equipment - safety (CB scheme)
|
IEC 60950-1 (2
nd Edition)
|
Rail applications
|
EN 50121-4
|
Overvoltage category (EN 62477-1)
|
III
|
Connection data, input
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
6 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
4 mm²
|
Conductor cross section AWG min.
|
14
|
Conductor cross section AWG max.
|
10
|
Stripping length
|
7 mm
|
Screw thread
|
M3
|
Output data
|
Nominal output voltage
|
48 V DC ±1 %
|
Setting range of the output voltage (U
Set)
|
30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted)
|
Nominal output current (I
N)
|
20 A (-25 °C ... 60 °C, U
OUT = 48 V DC)
|
POWER BOOST (I
Boost)
|
22.5 A (-25°C ... 40°C permanent, U
OUT = 48 V DC )
|
Selective Fuse Breaking (I
SFB)
|
100 A (12 ms)
|
Derating
|
60 °C ... 70 °C (2.5%/K)
|
Connection in parallel
|
Yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback resistance
|
max. 60 V DC
|
Protection against surge voltage on the output
|
< 60 V DC
|
Active current limitation
|
Approx. I
BOOST = 22.5 A (for short-circuit)
|
Control deviation
|
< 1 % (change in load, static 10 % ... 90 %)
|
|
< 3 % (change in load, dynamic 10 % ... 90 %)
|
|
< 0.1 % (change in input voltage ±10 %)
|
Residual ripple
|
< 50 mV
PP (with nominal values)
|
Output power
|
960 W
|
Typical response time
|
< 0.65 s
|
Maximum power dissipation in no-load condition
|
12 W
|
Power loss nominal load max.
|
74 W
|
Connection data for signaling
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
6 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
4 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
10
|
Screw thread
|
M3
|
Dimensions
|
Width
|
180 mm
|
Height
|
130 mm
|
Depth
|
125 mm
|
Width with alternative assembly
|
122 mm
|
Height with alternative assembly
|
130 mm
|
Depth with alternative assembly
|
183 mm
|
Weight per piece
|
3300.0 GRM
|
Input data
|
Nominal input voltage range
|
100 V AC ... 240 V AC
|
|
120 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
|
Input voltage range
|
85 V AC ... 264 V AC
|
|
90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
|
Dielectric strength maximum
|
300 V AC
|
AC frequency range
|
45 Hz ... 65 Hz
|
Frequency range DC
|
0 Hz
|
Discharge current to PE
|
< 3.5 mA
|
Current consumption
|
8.7 A (120 V AC)
|
|
4.5 A (230 V AC)
|
|
9.4 A (110 V DC)
|
|
4.6 A (220 V DC)
|
Nominal power consumption
|
1046 VA
|
Inrush surge current
|
< 15 A (typical)
|
Mains buffering
|
typ. 20 ms (120 V AC)
|
|
typ. 22 ms (230 V AC)
|
Input fuse
|
20 A (fast blow, internal)
|
Choice of suitable circuit breakers
|
6 A ... 16 A (AC: Characteristics B, C, D, K)
|
Type of protection
|
Transient surge protection
|
Protective circuit/component
|
Varistor
|
Connection data, onput
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.5 mm²
|
Conductor cross section solid max.
|
16 mm²
|
Conductor cross section flexible min.
|
0.5 mm²
|
Conductor cross section flexible max.
|
16 mm²
|
Conductor cross section AWG min.
|
8
|
Conductor cross section AWG max.
|
6
|
Stripping length
|
10 mm
|
Screw thread
|
M3
|
Ambient conditions
|
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Installation height
|
6000 m
|
Approvals
|
|
- DNV GL
- EAC
- UL Recognized
- CSA
- IECEE CB Scheme
- UL Listed
|