Environmental Product Compliance
|
REACH SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
General
|
Net weight
|
1 kg
|
Efficiency
|
typ. 90 % (120 V AC)
|
|
typ. 91.5 % (230 V AC)
|
Insulation voltage input/output
|
3 kV AC (type test)
|
|
1.5 kV AC (routine test)
|
Protection class
|
I (in closed control cabinet)
|
Degree of protection
|
IP20
|
MTBF (IEC 61709, SN 29500)
|
> 1800000 h (25 °C)
|
|
> 1000000 h (40 °C)
|
|
> 480000 h (60 °C)
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: horizontally 0 mm (≤ 40 °C) 10 mm (≤ 70 °C), vertically 50 mm
|
Standards and Regulations
|
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Noise emission
|
EN 55011 (EN 55022)
|
Noise immunity
|
EN 61000-6-2:2005
|
Standards/regulations
|
EN 61000-4-2
|
Contact discharge
|
4 kV (Test Level 2)
|
Standards/regulations
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
1.4 GHz ... 2 GHz
|
Test field strength
|
3 V/m (Test Level 2)
|
Standards/regulations
|
EN 61000-4-4
|
Comments
|
Criterion B
|
Standards/regulations
|
EN 61000-6-3
|
|
EN 61000-4-6
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Low Voltage Directive
|
Conformance with LV directive 2006/95/EC
|
Standard - Safety of transformers
|
EN 61558-2-16 (air clearances and creepage distances only)
|
Standard - Electrical safety
|
IEC 60950-1/VDE 0805 (SELV)
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
|
EN 50178/VDE 0160 (PELV)
|
Standard – Safety extra-low voltage
|
IEC 60950-1 (SELV) and EN 60204-1 (PELV)
|
Standard - Safe isolation
|
DIN VDE 0100-410
|
Standard – Limitation of mains harmonic currents
|
EN 61000-3-2
|
Shipbuilding approval
|
DNV GL (EMC B)
|
UL approvals
|
UL Listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
Shock
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
Vibration (operation)
|
< 25 Hz, amplitude ±1.6 mm (according to DNV GL CG-0339)
|
|
15 Hz ... 150 Hz, 4g, 90 min.
|
Approval - requirement of the semiconductor industry with regard to mains voltage dips
|
Semi F47-0706
|
Rail applications
|
EN 50121-4
|
Connection data, input
|
Connection method
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
4 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
12
|
Stripping length
|
10 mm
|
Output data
|
Nominal output voltage
|
24 V DC ±1 %
|
Setting range of the output voltage (USet)
|
24 V DC ... 28 V DC (constant capacity)
|
Nominal output current (IN)
|
10 A
|
Dynamic Boost (IDyn.Boost)
|
15 A (5 s)
|
Derating
|
> 60 °C ... 70 °C (2.5%/K)
|
Connection in parallel
|
Yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback resistance
|
≤ 35 V DC
|
Protection against surge voltage on the output
|
≤ 30 V DC
|
Control deviation
|
< 1 % (change in load, static 10 % ... 90 %)
|
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
|
|
< 0.1 % (change in input voltage ±10 %)
|
Residual ripple
|
< 20 mVPP (with nominal values)
|
Output power
|
240 W
|
Typical response time
|
< 1 s
|
Maximum power dissipation in no-load condition
|
< 5.1 W
|
Power loss nominal load max.
|
< 25 W
|
Connection data for signaling
|
Connection method
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
1.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
1.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
16
|
Stripping length
|
8 mm
|
Dimensions
|
Width
|
42 mm
|
Height
|
130 mm
|
Depth
|
160 mm
|
Weight per piece
|
1188.2 GRM
|
Input data
|
Nominal input voltage range
|
100 V AC ... 240 V AC
|
|
110 V DC ... 250 V DC
|
Input voltage range
|
100 V AC ... 240 V AC -15 % ... +10 %
|
|
110 V DC ... 250 V DC -10 % ... +10 %
|
Dielectric strength maximum
|
300 V AC 15 s
|
AC frequency range
|
50 Hz ... 60 Hz ±5 Hz
|
Discharge current to PE
|
< 3.5 mA
|
Current consumption
|
3.1 A (100 V AC)
|
|
2.4 A (120 V AC)
|
|
1.3 A (230 V AC)
|
|
1.4 A (240 V AC)
|
Nominal power consumption
|
285 VA
|
Inrush surge current
|
typ. 20 A
|
Mains buffering
|
typ. 20 ms (120 V AC)
|
|
typ. 20 ms (230 V AC)
|
Input fuse
|
6.3 A (internal (device protection))
|
Choice of suitable circuit breakers
|
6 A ... 16 A (Characteristics B, C, D, K)
|
Power factor (cos phi)
|
0.93
|
Type of protection
|
Transient surge protection
|
Protective circuit/component
|
Varistor
|
Connection data, onput
|
Connection method
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
4 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
12
|
Stripping length
|
8 mm
|
Ambient conditions
|
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Installation height
|
≤ 5000 m (> 2000 m, observe derating)
|
Approvals
|
|
- cULus Listed
- DNV GL
- cULus Recognized
- EAC
- UL Recognized
- BSH
- cUL Recognized
- cUL Listed
- UL Listed
|