Environmental Product Compliance
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
General
|
Net weight
|
0.188 kg
|
Efficiency
|
typ. 89.2 % (120 V AC)
|
|
typ. 90.7 % (230 V AC)
|
Insulation voltage input/output
|
4 kV AC (type test)
|
|
3 kV AC (routine test)
|
Protection class
|
II
|
Degree of protection
|
IP20
|
MTBF (IEC 61709, SN 29500)
|
> 1904000 h (25 °C)
|
|
> 1107000 h (40 °C)
|
|
> 486000 h (60 °C)
|
Assembly instructions
|
DIN rail mounting
|
Standards and Regulations
|
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Standards/regulations
|
EN 61000-4-2
|
Contact discharge
|
4 kV (Test Level 2)
|
Standards/regulations
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
1.4 GHz ... 2 GHz
|
Test field strength
|
3 V/m (Test Level 2)
|
Standards/regulations
|
EN 61000-4-4
|
Comments
|
Criterion B
|
Standards/regulations
|
EN 61000-4-6
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Conducted noise emission
|
EN 55016 EN 61000-6-4 (Class A)
|
Standards/regulations
|
EN 61000-4-8
|
|
EN 61000-4-11
|
|
EN 61000-4-9
|
|
EN 61000-4-12
|
|
EN 61000-4-16
|
Standard - Safety of transformers
|
EN 61558-2-16
|
Standard - Electrical safety
|
IEC 61010-2-201 (SELV)
|
Standard - power supply devices for low voltage with DC output
|
EN 61204-3
|
Standard – Safety extra-low voltage
|
IEC 61010-1 (SELV)
|
|
IEC 61010-2-201 (PELV)
|
Standard - Safe isolation
|
IEC 61558-2-16
|
|
IEC 61010-2-201
|
Standard – Limitation of mains harmonic currents
|
EN 61000-3-2
|
UL approvals
|
UL Listed UL 61010-1
|
|
UL Listed UL 61010-2-201
|
|
UL 1310 Class 2 Power Units
|
|
ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
Shock
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
Vibration (operation)
|
< 15 Hz, ±2.5 mm amplitude; 15 Hz ... 100 Hz: 2.3 g 90 Min. (in accordance with IEC 60068-2-6)
|
Overvoltage category (EN 61010-1)
|
II (≤ 5000 m)
|
Overvoltage category (EN 62477-1)
|
III (≤ 2000 m)
|
Connection data, input
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.14 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.14 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
26
|
Conductor cross section AWG max.
|
14
|
Stripping length
|
8 mm
|
Output data
|
Nominal output voltage
|
24 V DC
|
Setting range of the output voltage (USet)
|
24 V DC ... 28 V DC (constant capacity)
|
Nominal output current (IN)
|
1.3 A
|
Static Boost (IStat.Boost)
|
1.625 A (≤ 40 °C)
|
Dynamic Boost (IDyn.Boost)
|
2.6 A (≤ 60 °C (5 s))
|
Derating
|
> 60 °C (2.5%/K)
|
Connection in parallel
|
Yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback resistance
|
≤ 35 V DC
|
Protection against surge voltage on the output
|
≤ 32 V DC
|
Control deviation
|
< 0.5 % (Static load change 10 % ... 90 %)
|
|
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
|
|
< 0.1 % (change in input voltage ±10 %)
|
Residual ripple
|
< 40 mVPP (with nominal values)
|
Output power
|
30 W
|
Typical response time
|
500 ms
|
Maximum power dissipation in no-load condition
|
< 0.4 W (230 V AC)
|
|
< 0.4 W (120 V AC)
|
Power loss nominal load max.
|
< 3.7 W (120 V AC)
|
|
< 3.1 W (230 V AC)
|
Connection data for signaling
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.14 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.14 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
26
|
Conductor cross section AWG max.
|
14
|
Stripping length
|
8 mm
|
Dimensions
|
|
Width
|
22.5 mm
|
Height
|
99 mm
|
Depth
|
90 mm
|
Weight per piece
|
245.0 GRM
|
Input data
|
Input voltage range
|
100 V AC ... 240 V AC -15 % ... +10 %
|
|
110 V DC ... 250 V DC -20 % ... +40 %
|
Dielectric strength maximum
|
300 V AC 30 s
|
Discharge current to PE
|
< 0.25 mA (264 V AC, 60 Hz)
|
Current consumption
|
0.46 A (100 V AC)
|
|
0.37 A (120 V AC)
|
|
0.2 A (230 V AC)
|
|
0.2 A (240 V AC)
|
Nominal power consumption
|
37 VA
|
Inrush surge current
|
typ. 14 A (at 25 °C)
|
Mains buffering
|
typ. 43 ms (120 V AC)
|
|
typ. 43 ms (230 V AC)
|
Input fuse
|
3.15 A (slow-blow, internal)
|
Choice of suitable circuit breakers
|
6 A ... 16 A (Characteristic B, C or comparable)
|
Type of protection
|
Transient surge protection
|
Protective circuit/component
|
Varistor
|
Connection data, onput
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.14 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.14 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
26
|
Conductor cross section AWG max.
|
14
|
Stripping length
|
8 mm
|
Ambient conditions
|
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Installation height
|
≤ 5000 m (> 2000 m, observe derating)
|
Approvals
|
|
- cULus Listed
- DNV GL
- EAC
- cUL Listed
- IECEE CB Scheme
- UL Listed
|