Environmental Product Compliance
|
REACH SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
General
|
Net weight
|
1.3 kg
|
Efficiency
|
typ. 92.4 % (120 V AC)
|
|
typ. 94 % (230 V AC)
|
Insulation voltage input/output
|
4 kV AC (type test)
|
|
2 kV AC (routine test)
|
Insulation voltage input / PE
|
3.5 kV AC (type test)
|
|
2.4 kV AC (routine test)
|
Insulation voltage output / PE
|
0.5 kV DC (type test)
|
|
0.5 kV DC (routine test)
|
Protection class
|
I
|
Degree of protection
|
IP20
|
MTBF (IEC 61709, SN 29500)
|
> 1110000 h (25 °C)
|
|
> 673000 h (40 °C)
|
|
> 309000 h (60 °C)
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
|
Standards and Regulations
|
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Noise emission
|
Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
|
Noise immunity
|
Immunity according to EN 61000-6-1 (residential), EN 61000-6-2 (industrial), and EN 61000-6-5 (power station equipment zone), IEC/EN 61850-3 (energy supply)
|
Standards/regulations
|
EN 61000-4-2
|
Contact discharge
|
4 kV (Test Level 2)
|
Standards/regulations
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
1.4 GHz ... 2 GHz
|
Test field strength
|
3 V/m (Test Level 2)
|
Standards/regulations
|
EN 61000-4-4
|
Comments
|
Criterion B
|
Standards/regulations
|
EN 61000-4-6
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Conducted noise emission
|
EN 55016 EN 61000-6-4 (Class A)
|
Standards/regulations
|
EN 61000-4-8
|
|
EN 61000-4-11
|
|
EN 61000-4-9
|
|
EN 61000-4-12
|
|
EN 61000-4-16
|
|
EN 61000-4-18
|
Low Voltage Directive
|
Conformance with Low Voltage Directive 2014/35/EC
|
Standard - Safety of transformers
|
EN 61558-2-16 (air clearances and creepage distances only)
|
Standard - Electrical safety
|
IEC 60950-1/VDE 0805 (SELV)
|
Standard - power supply devices for low voltage with DC output
|
EN 61204-3
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
|
EN 50178/VDE 0160 (PELV)
|
Standard – Safety extra-low voltage
|
IEC 60950-1 (SELV)
|
|
EN 60204-1 (PELV)
|
Standard - Safe isolation
|
DIN VDE 0100-410
|
Standard – Limitation of mains harmonic currents
|
EN 61000-3-2
|
Shipbuilding approval
|
DNV GL, PRS, BV, LR, ABS
|
UL approvals
|
UL Listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
Shock
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
Vibration (operation)
|
5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
|
Approval - requirement of the semiconductor industry with regard to mains voltage dips
|
SEMI F47-0706; EN 61000-4-11
|
Rail applications
|
EN 50121-3-2
|
Overvoltage category (EN 60950-1)
|
II (≤ 5000 m)
|
Overvoltage category (EN 61010-1)
|
II (≤ 5000 m)
|
Overvoltage category (EN 62477-1)
|
III (≤ 2000 m)
|
Connection data, input
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
6 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
4 mm²
|
Conductor cross section AWG min.
|
30
|
Conductor cross section AWG max.
|
10
|
Stripping length
|
8 mm
|
Output data
|
Nominal output voltage
|
24 V DC
|
Setting range of the output voltage (USet)
|
24 V DC ... 29.5 V DC (constant capacity)
|
Nominal output current (IN)
|
20 A
|
Static Boost (IStat.Boost)
|
25 A
|
Dynamic Boost (IDyn.Boost)
|
30 A (5 s)
|
Selective Fuse Breaking (ISFB)
|
120 A (15 ms)
|
Derating
|
> 60 °C (2.5%/K)
|
Connection in parallel
|
Yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback resistance
|
≤ 35 V DC
|
Protection against surge voltage on the output
|
≤ 32 V DC
|
Control deviation
|
< 0.5 % (Static load change 10 % ... 90 %)
|
|
< 4 % (Dynamic load change 10 % ... 90 %, (10 Hz))
|
|
< 0.25 % (change in input voltage ±10 %)
|
Residual ripple
|
< 50 mVPP (with nominal values)
|
Output power
|
480 W
|
Typical response time
|
300 ms (from SLEEP MODE)
|
Maximum power dissipation in no-load condition
|
< 5 W (120 V AC)
|
|
< 5 W (230 V AC)
|
Power loss nominal load max.
|
< 40 W (120 V AC)
|
|
< 32 W (230 V AC)
|
Connection data for signaling
|
Connection method
|
Push-in connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
1.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
1.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
16
|
Stripping length
|
8 mm
|
Dimensions
|
|
Width
|
70 mm
|
Height
|
130 mm
|
Depth
|
125 mm
|
Width with alternative assembly
|
122 mm
|
Height with alternative assembly
|
130 mm
|
Depth with alternative assembly
|
73 mm
|
Weight per piece
|
1593.0 GRM
|
Input data
|
Nominal input voltage range
|
100 V AC ... 240 V AC
|
|
110 V DC ... 250 V DC
|
Input voltage range
|
100 V AC ... 240 V AC -15 % ... +10 %
|
|
110 V DC ... 250 V DC -18 % ... +40 %
|
Dielectric strength maximum
|
300 V AC 60 s
|
AC frequency range
|
50 Hz ... 60 Hz -10 % ... +10 %
|
Discharge current to PE
|
< 3.5 mA
|
Current consumption
|
6.8 A (100 V AC)
|
|
5.5 A (120 V AC)
|
|
2.8 A (230 V AC)
|
|
2.7 A (240 V AC)
|
Nominal power consumption
|
520 VA
|
Inrush surge current
|
typ. 11 A (at 25 °C)
|
Mains buffering
|
typ. 28 ms (120 V AC)
|
|
typ. 29 ms (230 V AC)
|
Input fuse
|
12 A (slow-blow, internal)
|
Choice of suitable circuit breakers
|
10 A ... 16 A (Characteristic B, C, D, K or comparable)
|
Type of protection
|
Transient surge protection
|
Protective circuit/component
|
Varistor, gas-filled surge arrester
|
Connection data, onput
|
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
6 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
4 mm²
|
Conductor cross section AWG min.
|
30
|
Conductor cross section AWG max.
|
10
|
Stripping length
|
8 mm
|
Ambient conditions
|
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Installation height
|
≤ 5000 m (> 2000 m, observe derating)
|
Approvals
|
|
- ABS
- DNV GL
- BV
- PRS
- cUL Recognized
- cUL Listed
- LR
- UL Listed
- cULus Listed
- cULus Recognized
- UL Recognized
- EAC
- CSA
- Bauartgeprüft
|