ioLogik E2212 Specifications
|
• Inputs and Outputs
|
Digital Inputs
|
8 channels
|
Digital Outputs
|
8 channels
|
Configurable DI/Os
|
4 channels
|
Isolation
|
3k VDC or 2k Vrms
|
• Digital Input
|
Sensor Type
|
Wet Contact (NPN or PNP) and Dry Contact
|
I/O Mode
|
DI or Event Counter
|
Dry Contact
|
• On: short to GND
• Off: open
|
Wet Contact (DI to GND)
|
• On: 0 to 3 VDC
• OFF: 10 to 30 VDC
|
Common Type
|
6 points per COM
|
Counter Frequency
|
900 Hz
|
Digital Filtering Time Interval
|
Software Configurable
|
• Digital Output
|
Type
|
Sink
|
I/O Mode
|
DO or Pulse Output
|
Pulse Output Frequency
|
1 kHz
|
Over-voltage Protection
|
45 VDC
|
Over-current Protection
|
2.6 A (4 channels @650 mA)
|
Over-temperature Shutdown
|
175°C (min.)
|
Current Rating
|
200 mA per channel
|
• Power Requirements
|
Power Consumption
|
136 mA @ 24 VDC
|
• MTBF (mean time between failures)
|
Time
|
217,722 hrs
|
Database
|
Telcordia (Bellcore)
|
Common Specifications
|
• LAN
|
Ethernet
|
1 10/100 Mbps RJ45 port
|
Protection
|
1.5 kV magnetic isolation
|
Protocols
|
Modbus/TCP, TCP/IP, UDP, DHCP, BOOTP, SNMP, HTTP, CGI, SNTP, SMTP
|
• Serial Communication
|
Interface
|
RS-485-2w: Data+, Data-, GND (3-contact terminal block)
|
Serial Line Protection
|
15 kV ESD for all signals
|
• Serial Communication Parameters
|
Parity
|
None
|
Data Bits
|
8
|
Stop Bits
|
1
|
Flow Control
|
None
|
Baudrate
|
1200 to 115200 bps
|
Protocol
|
Modbus/RTU
|
• Power Requirements
|
Power Input
|
24 VDC nominal, 12 to 36 VDC
|
• Physical Characteristics
|
Wiring
|
I/O cable max. 14 AWG
|
Dimensions
|
115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in)
|
Weight
|
under 250 g
|
Mounting
|
DIN rail or wall
|
• Environmental Limits
|
Operating Temperature
|
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
Ambient Relative Humidity
|
5 to 95% (non-condensing)
|
Altitude
|
Up to 2000 m
|
Note
|
Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
|
• Standards and Certifications
|
Safety
|
UL 508
|
EMI
|
EN 61000-3-2; EN 61000-3-3; EN 61000-6-4;
FCC Part 15, Subpart B, Class A
|
EMS
|
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11, EN 61000-6-2
|
Shock
|
IEC 60068-2-27
|
Freefall
|
IEC 60068-2-32
|
Vibration
|
IEC 60068-2-6
|
Green Product
|
RoHS, CRoHS, WEEE
|
Note
|
Please check Moxa’s website for the most up-to-date certification status.
|
• Warranty
|
Warranty Period
|
5 years (excluding ioLogik E2214*)
|
*Note
|
Because of the limited lifetime of power relays, products that use that component are covered by a 2-year warranty.
|
Details
|
See www.moxa.com/warranty
|