• Inputs and Outputs
|
Digital Inputs
|
6 channels
|
Relay Outputs
|
6 channels
|
• Digital Input
|
Sensor Type
|
Wet Contact (NPN or PNP), Dry Contact
|
I/O Mode
|
DI or Event Counter
|
Dry Contact
|
• On: short to GND
• Off: open
|
Wet Contact
|
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
|
Isolation
|
3K VDC or 2K Vrms
|
Counter Frequency
|
250 Hz, power off storage
|
• Relay Output
|
Type
|
Form A (N.O.) relay outputs, 5A
|
Contact Rating
|
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110 VAC
|
Inductance Load
|
2 A
|
Resistance Load
|
5 A
|
Breakdown Voltage
|
500 VAC
|
Relay On/Off Time
|
1500 ms (Max.)
|
Initial Insulation Resistance
|
1G min. @ 500 VDC
|
Expected Life
|
100,000 times (Typical)
|
Initial Contact Resistance
|
30 milli-ohms (Max.)
|
Pulse Output
|
0.3 Hz at rated load
|
• LAN
|
Ethernet
|
2 x 10/100 Mbps switch ports, RJ45
|
Protection
|
1.5 KV magnetic isolation
|
Protocols
|
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP
|
• Power Requirements
|
Power Input
|
24 VDC nominal, 12 to 36 VDC
|
Power Consumption
|
188 mA @ 24 VDC
|
• Physical Characteristics
|
Wiring
|
I/O cable max. 14 AWG
|
Dimensions
|
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
|
Weight
|
under 200 g
|
• Environmental Limits
|
Operating Temperature
|
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
Ambient Relative Humidity
|
5 to 95% (non-condensing)
|
Altitude
|
Up to 2000 m and higher altitude on demand
|
• Standards and Certifications
|
Safety
|
UL 508
|
EMI
|
FCC Part 15 Subpart B Class A
|
EMS
|
IEC 61000-4, IEC 61000-6
|
Shock
|
IEC 60068-2-27
|
Freefall
|
IEC 60068-2-32
|
Vibration
|
IEC 60068-2-6
|
Hazardous Location
|
UL/cUL Class I Division 2, ATEX Zone 2
|
• MTBF (mean time between failures)
|
Time
|
808,744 hrs
|
Database
|
Telcordia (Bellcore)
|
• Warranty
|
Warranty Period
|
2 years
|
Details
|
See www.moxa.com/warranty
|