The MGate 5102-PBM-PN gateway provides a communication portal between
PROFIBUS devices (e.g., PROFIBUS PLC or drive) and the PROFINET host.
All models are protected with a rugged metallic casing, are DIN rail
mountable, and offer optional built-in optical isolation. The PROFIBUS
and Ethernet status LED indicators are provided for easy maintenance.
The rugged design is suitable for industrial applications such as oil
& gas, power, process automation, and factory automation.
• PROFIBUS Interface
|
Protocol
|
PROFIBUS DP-V1 Master
|
Number of Ports
|
1
|
Data Rate
|
9600 bps to 12 Mbps
|
Connector
|
DB9 female
|
Isolation
|
2 KV (built-in)
|
• Ethernet Interface
|
Protocol
|
PROFINET RT
|
Number of Ports
|
2 (1 IP)
|
Speed
|
10/100 Mbps, Auto MDI/MDIX
|
Connector
|
8-pin RJ45
|
Magnetic Isolation Protection
|
1.5 KV built-in
|
• Serial Signals (Serial Console)
|
Connector
|
8-pin RJ45
|
RS-232
|
TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
|
• Software
|
Configuration Options
|
Windows utility, serial console, web console (HTTP/HTTPS), Telnet/SSH console
|
Utilities
|
MGate Manager for Windows 2000, Windows XP/2003/Vista/2008/7 x86/x64
|
• Physical Characteristics
|
Housing
|
Metal
|
Weight
|
500 g
|
Dimensions
|
36 x 105 x 140 mm (1.42 x 4.13 x 5.51 in)
|
• Environmental Limits
|
Operating Temperature
|
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to 167°F)
|
Storage Temperature
|
-40 to 85°C (-40 to 185°F)
|
Ambient Relative Humidity
|
5 to 95% (non-condensing)
|
• Power Requirements
|
Input Voltage
|
12 to 48 VDC
|
Power Connector
|
Terminal block
|
Power Consumption
|
365 mA @ 12 VDC
|
• Standards and Certifications
|
Safety
|
UL 508, EN 60950-1
|
Hazardous Location
|
UL/cUL Class 1 Division 2 Groups A/B/C/D, ATEX Zone 2 (pending)
|
EMC
|
CE, FCC
|
EMI
|
EN 55022 Class A, FCC Part 15 Subpart B Class A
|
EMS
|
EN 55024,
EN 61000-4-2 (ESD) Level 3,
EN 61000-4-3 (RS) Level 3,
EN 61000-4-4 (EFT) Level 4,
EN 61000-4-5 (Surge) Level 3,
EN 61000-4-6 (CS) Level 3,
EN 61000-4-8,
EN 61000-4-11,
EN 61000-4-12
|
Shock
|
IEC 60068-2-27
|
Freefall
|
IEC 60068-2-32
|
Vibration
|
IEC 60068-2-6
|
• Reliability
|
MTBF (mean time between failures)
|
980,417 hrs
|
• Warranty
|
Warranty Period
|
5 years
|
Details
|
See www.moxa.com/warranty
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Features
- Protocol conversion between PROFIBUS and PROFINET
- Automatic scan of PROFIBUS devices, and easy configuration
- microSD card for configuration backup
- Built-in Ethernet cascading for easy wiring
- Redundant dual DC power inputs and relay output supported
- Embedded I/O monitoring and and diagnostic tools
- Web-based GUI for I/O data visualization
- -40 to 75°C wide operating temperature models available
|
|
|
|
|
|
|